Height |
N/A 24 in |
Width |
N/A 24 in |
Length |
N/A 3 in |
Intended Application |
N/A Heating, Ventilation, and Air Conditioning (HVAC) |
Industry Standards / Certifications |
N/A American Society for Testing and Materials (ASTM) National Voluntary Laboratory Accreditation Program (NVLAP®) National Fire Protection Association (NFPA) Underwriters Laboratories (UL) |
Shape |
N/A Rectangular |
Dynamic Insertion Loss @ 63 Hertz (Hz), Octave Band 1, Face Velocity -2000 Feet per Minute (FPM) |
N/A 7 dB |
Dynamic Insertion Loss @ 63 Hertz (Hz), Octave Band 1, Face Velocity -1000 Feet per Minute (FPM) |
N/A 6 dB |
Dynamic Insertion Loss @ 63 Hertz (Hz), Octave Band 1, Face Velocity 0 Feet per Minute (FPM) |
N/A 9 dB |
Dynamic Insertion Loss @ 63 Hertz (Hz), Octave Band 1, Face Velocity +1000 Feet per Minute (FPM) |
N/A 8 dB |
Dynamic Insertion Loss @ 63 Hertz (Hz), Octave Band 1, Face Velocity +2000 Feet per Minute (FPM) |
N/A 8 dB |
Dynamic Insertion Loss @ 125 Hertz (Hz), Octave Band 2, Face Velocity -2000 Feet per Minute (FPM) |
N/A 11 dB |
Dynamic Insertion Loss @ 125 Hertz (Hz), Octave Band 2, Face Velocity -1000 Feet per Minute (FPM) |
N/A 10 dB |
Dynamic Insertion Loss @ 125 Hertz (Hz), Octave Band 2, Face Velocity 0 Feet per Minute (FPM) |
N/A 9 dB |
Dynamic Insertion Loss @ 125 Hertz (Hz), Octave Band 2, Face Velocity +1000 Feet per Minute (FPM) |
N/A 9 dB |
Dynamic Insertion Loss @ 125 Hertz (Hz), Octave Band 2, Face Velocity +2000 Feet per Minute (FPM) |
N/A 8 dB |
Dynamic Insertion Loss @ 250 Hertz (Hz), Octave Band 3, Face Velocity -2000 Feet per Minute (FPM) |
N/A 14 dB |
Dynamic Insertion Loss @ 250 Hertz (Hz), Octave Band 3, Face Velocity -1000 Feet per Minute (FPM) |
N/A 16 dB |
Dynamic Insertion Loss @ 250 Hertz (Hz), Octave Band 3, Face Velocity 0 Feet per Minute (FPM) |
N/A 15 dB |
Dynamic Insertion Loss @ 250 Hertz (Hz), Octave Band 3, Face Velocity +1000 Feet per Minute (FPM) |
N/A 14 dB |
Dynamic Insertion Loss @ 250 Hertz (Hz), Octave Band 3, Face Velocity +2000 Feet per Minute (FPM) |
N/A 12 dB |
Dynamic Insertion Loss @ 500 Hertz (Hz), Octave Band 4, Face Velocity -2000 Feet per Minute (FPM) |
N/A 23 dB |
Dynamic Insertion Loss @ 500 Hertz (Hz), Octave Band 4, Face Velocity -1000 Feet per Minute (FPM) |
N/A 25 dB |
Dynamic Insertion Loss @ 500 Hertz (Hz), Octave Band 4, Face Velocity 0 Feet per Minute (FPM) |
N/A 24 dB |
Dynamic Insertion Loss @ 500 Hertz (Hz), Octave Band 4, Face Velocity +1000 Feet per Minute (FPM) |
N/A 23 dB |
Dynamic Insertion Loss @ 500 Hertz (Hz), Octave Band 4, Face Velocity +2000 Feet per Minute (FPM) |
N/A 19 dB |
Dynamic Insertion Loss @ 1000 Hertz (Hz), Octave Band 5, Face Velocity -2000 Feet per Minute (FPM) |
N/A 36 dB |
Dynamic Insertion Loss @ 1000 Hertz (Hz), Octave Band 5, Face Velocity -1000 Feet per Minute (FPM) |
N/A 36 dB |
Dynamic Insertion Loss @ 1000 Hertz (Hz), Octave Band 5, Face Velocity 0 Feet per Minute (FPM) |
N/A 35 dB |
Dynamic Insertion Loss @ 1000 Hertz (Hz), Octave Band 5, Face Velocity +1000 Feet per Minute (FPM) |
N/A 33 dB |
Dynamic Insertion Loss @ 1000 Hertz (Hz), Octave Band 5, Face Velocity +2000 Feet per Minute (FPM) |
N/A 30 dB |
Dynamic Insertion Loss @ 2000 Hertz (Hz), Octave Band 6, Face Velocity -2000 Feet per Minute (FPM) |
N/A 36 dB |
Dynamic Insertion Loss @ 2000 Hertz (Hz), Octave Band 6, Face Velocity -1000 Feet per Minute (FPM) |
N/A 37 dB |
Dynamic Insertion Loss @ 2000 Hertz (Hz), Octave Band 6, Face Velocity 0 Feet per Minute (FPM) |
N/A 38 dB |
Dynamic Insertion Loss @ 2000 Hertz (Hz), Octave Band 6, Face Velocity +1000 Feet per Minute (FPM) |
N/A 38 dB |
Dynamic Insertion Loss @ 2000 Hertz (Hz), Octave Band 6, Face Velocity +2000 Feet per Minute (FPM) |
N/A 37 dB |
Dynamic Insertion Loss @ 4000 Hertz (Hz), Octave Band 7, Face Velocity -2000 Feet per Minute (FPM) |
N/A 23 dB |
Dynamic Insertion Loss @ 4000 Hertz (Hz), Octave Band 7, Face Velocity -1000 Feet per Minute (FPM) |
N/A 22 dB |
Dynamic Insertion Loss @ 4000 Hertz (Hz), Octave Band 7, Face Velocity 0 Feet per Minute (FPM) |
N/A 26 dB |
Dynamic Insertion Loss @ 4000 Hertz (Hz), Octave Band 7, Face Velocity +1000 Feet per Minute (FPM) |
N/A 27 dB |
Dynamic Insertion Loss @ 4000 Hertz (Hz), Octave Band 7, Face Velocity +2000 Feet per Minute (FPM) |
N/A 28 dB |
Dynamic Insertion Loss @ 8000 Hertz (Hz), Octave Band 8, Face Velocity -2000 Feet per Minute (FPM) |
N/A 15 dB |
Dynamic Insertion Loss @ 8000 Hertz (Hz), Octave Band 8, Face Velocity -1000 Feet per Minute (FPM) |
N/A 14 dB |
Dynamic Insertion Loss @ 8000 Hertz (Hz), Octave Band 8, Face Velocity 0 Feet per Minute (FPM) |
N/A 19 dB |
Dynamic Insertion Loss @ 8000 Hertz (Hz), Octave Band 8, Face Velocity +1000 Feet per Minute (FPM) |
N/A 21 dB |
Dynamic Insertion Loss @ 8000 Hertz (Hz), Octave Band 8, Face Velocity +2000 Feet per Minute (FPM) |
N/A 23 dB |
Self Generated Sound Power Rating (PWL) @ 2000 Hertz (Hz), Octave Band 6, -2000 Feet per Minute (FPM) |
N/A 61 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 4000 Hertz (Hz), Octave Band 7, +2000 Feet per Minute (FPM) |
N/A 61 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 4000 Hertz (Hz), Octave Band 7, +1000 Feet per Minute (FPM) |
N/A 37 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 4000 Hertz (Hz), Octave Band 7, -1000 Feet per Minute (FPM) |
N/A 57 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 4000 Hertz (Hz), Octave Band 7, -2000 Feet per Minute (FPM) |
N/A 67 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 8000 Hertz (Hz), Octave Band 8, +2000 Feet per Minute (FPM) |
N/A 58 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 8000 Hertz (Hz), Octave Band 8, +1000 Feet per Minute (FPM) |
N/A 32 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 8000 Hertz (Hz), Octave Band 8, -1000 Feet per Minute (FPM) |
N/A 51 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 8000 Hertz (Hz), Octave Band 8, -2000 Feet per Minute (FPM) |
N/A 64 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 63 Hertz (Hz), Octave Band 1, +2000 Feet per Minute (FPM) |
N/A 67 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 63 Hertz (Hz), Octave Band 1, +1000 Feet per Minute (FPM) |
N/A 52 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 63 Hertz (Hz), Octave Band 1, -1000 Feet per Minute (FPM) |
N/A 52 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 63 Hertz (Hz), Octave Band 1, -2000 Feet per Minute (FPM) |
N/A 57 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 125 Hertz (Hz), Octave Band 2, +2000 Feet per Minute (FPM) |
N/A 64 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 125 Hertz (Hz), Octave Band 2, +1000 Feet per Minute (FPM) |
N/A 48 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 125 Hertz (Hz), Octave Band 2, -1000 Feet per Minute (FPM) |
N/A 45 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 125 Hertz (Hz), Octave Band 2, -2000 Feet per Minute (FPM) |
N/A 52 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 250 Hertz (Hz), Octave Band 3, +2000 Feet per Minute (FPM) |
N/A 61 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 250 Hertz (Hz), Octave Band 3, +1000 Feet per Minute (FPM) |
N/A 42 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 250 Hertz (Hz), Octave Band 3, -1000 Feet per Minute (FPM) |
N/A 48 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 250 Hertz (Hz), Octave Band 3, -2000 Feet per Minute (FPM) |
N/A 52 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 500 Hertz (Hz), Octave Band 4, +2000 Feet per Minute (FPM) |
N/A 58 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 500 Hertz (Hz), Octave Band 4, +1000 Feet per Minute (FPM) |
N/A 39 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 500 Hertz (Hz), Octave Band 4, -1000 Feet per Minute (FPM) |
N/A 51 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 500 Hertz (Hz), Octave Band 4, -2000 Feet per Minute (FPM) |
N/A 55 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 1000 Hertz (Hz), Octave Band 4, +2000 Feet per Minute (FPM) |
N/A 54 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 1000 Hertz (Hz), Octave Band 4, +1000 Feet per Minute (FPM) |
N/A 41 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 1000 Hertz (Hz), Octave Band 4, -1000 Feet per Minute (FPM) |
N/A 53 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 1000 Hertz (Hz), Octave Band 4, -2000 Feet per Minute (FPM) |
N/A 57 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 2000 Hertz (Hz), Octave Band 6, +2000 Feet per Minute (FPM) |
N/A 57 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 2000 Hertz (Hz), Octave Band 6, +1000 Feet per Minute (FPM) |
N/A 43 dB re 10-12 watts |
Self Generated Sound Power Rating (PWL) @ 2000 Hertz (Hz), Octave Band 6, -1000 Feet per Minute (FPM) |
N/A 58 dB re 10-12 watts |
Additional Information |
N/A Other metals, acoustical fills, heavy-duty shell and components, and matching connections are available. ArtSilencer are also designed and manufactured for specialized applications where rigid design and noise reduction criteria, unique space limitations, adverse environments, or other special conditions preclude the use of standard models. |
Note |
N/A
This table contains both forward (+) and backward (-) flow acoustic and aerodynamic ratings based on test results measured in accordance with ASTM E477. Copies of these test reports can be furnished upon request. Air flow ratings shown include static regain. Therefore if silencers are installed immediately before or after elbows, transitions, at the intake or discharge of the system, or without duct, allowance to compensate for such conditions must be included when calculating the operating pressure loss thru the silencer. Failure to make allowance for these conditions can add several velocity heads to the pressure loss of the system. All acoustic and aerodynamic performance obtained on 24 inch x 24 inch cross section production units. |